Cart
Materials and equipment for your project
DOMIS DECOR — SPC and WPC wall panels
Climate control equipment and installation

Mixing unit USVK-1 1/4-10

Buy Mixing unit USVK-1 1/4-10 at Factory Prices
Mixing unit USVK-1 1/4-10
from
1,512.09 €
Ex Tax: 1,249.66 €
  • Availability: 99
  • Brand: Vents
  • Model: 8337
  • Weight: 50.00kg
  • UPC: 8337
  • JAN: 1187

Before placing an order, contact DOMIS.PRO to confirm delivery availability and arrangements for your chosen product, including the destination, delivery method, cost and timing.

For questions about returns or exchanges, contact DOMIS.PRO. Provide your order number and the product name so we can discuss your situation and the next steps.

Before ordering, check the specifications, dimensions and compatibility of the chosen product with your equipment or project.

If the product page does not provide enough information, ask DOMIS.PRO and include the model or product code. Confirm the supplied components and any specifications that matter to you before placing an order.

The mixing unit for ventilation Vents USVK-1 1/4-10 is designed to ensure circulation and control the temperature of water (water mixtures) used as a coolant in heat exchangers of ventilation systems. The maximum productivity of this unit is6.8 m3/h.

Design and description of operation

The design of the USWK is shown in Figure 1. Circulation pump 1 provides a continuous water flow of the required volume, while the temperature of the water entering the heat exchanger is regulated by mixing in a circulation ring of water coming from the network with return water coming from the heat exchanger. The amount of return water directed through jumper 4 is regulated by three-way valve 3 with electric drive 2, the control voltage of which is determined by the set temperature of the supply air leaving the heat exchanger.

'Design

Installation and maintenance

Connection is carried out by specialists authorized to perform such work. It is prohibited to operate the USVK outside the temperature range, as well as in rooms with aggressive impurities in the air and in an explosive environment. Before connecting the USVK to the network, you must ensure that there are no visible damages. When installing the water mixing unit, comply with the following conditions:

  • be sure to ensure a horizontal position of the motor shaft axis,
  • exclude the possibility of transferring mechanical loads to the water treatment unit from the connected pipelines,
  • exclude the possibility of accidental contact with the moving parts of the USVK supply wires.

Connection to the water main

The supply (discharge) of water to the USVK is carried out by direct connection to a stationary water main, or flexible metal-rubber hoses through a threaded connection with inlet and outlet pipes. The connection to the main line must be carried out in such a way as to exclude any loads leading to mechanical damage and violation of the tightness of the USVK. The pipelines should be connected in such a way that they can be quickly disconnected during repair work.

Electrical connection

All electrical connections must be carried out by persons with the necessary qualifications and approval. Before connecting, install protective grounding of the circulation pump. Do not allow the power cable to come into contact with the pipeline or pump.

Operating conditions

Permissible operating conditions of mixing units are determined by the set of elements included in its composition and are characterized by the following values:

  • ambient temperature, ° C ...........5-40
  • maximum pressure in the control channel, bar..........10

The pump motor bearings are lubricated by the pumped liquid. Single-phase pumps do not require additional overload protection. For three-phase pumps, external overload protection must be provided.

Transmittance

transmittance

'Transmission

, where


?pv100 - pressure loss when the valve is fully open,
V100 - nominal water flow at ?pv100.

Technical characteristics

OptionValue
Kvs of three-way valve 10
Connection diameter 1 1/4'
Circulation pump

DAB A56/180XM

Method of adjusting a three-way valve

Smooth 0…10 V

Three-way valve with electric drive

Belimo R329

Three-way valve drive

Belimo LR24A-SR

Connection Threaded
Nominal diameter of three-way valve DN 32
Unit maximum productivity, m3/h 6.8
Maximum unit pressure developed, kPa62
Ttemperature of the transported liquid, 0 C -10 +110
Maximum glycol content in the transported liquid, % 30
Number of pump speeds 3
Phasity 1
Maximum pump power, W271
Pump supply voltage, V 230
Weight, kg

7.4

Overall dimensions

'Drawing

DimensionsBH H1L
mm175355240500

Connection diagram

'Connection

T1 and T2 - supply and return pipelines of the heating network ,
P1 and P2 - liquid pressure meters in the heating network,
1 - USVK (mixing unit),
2- Water heater,
3 - Three-way valve with drive,
4 - Circulation pump,
5 - Shut-off valve,
6 - Supply and return pipelines from the heating network to the heater,
7 - Check valve,
< strong>8 - Balancing valve,
9 - Coarse filter.








Documentation

'Passport

Installation instructions

'Installation

Write a review

Please login or register to review
Brand: Vents
The mixing unit for ventilation Vents USVK-2-25 is designed to ensure circulation and control the temperature of water (water mixtures) used as a cool..
from
4,184.65 €
Ex Tax:3,458.39 €
Add to cart
Brand: Vents
The mixing unit for ventilation Vents USVK-1 1/2-16 is designed to ensure circulation and control the temperature of water (water mixtures) used as a ..
from
3,516.52 €
Ex Tax:2,906.21 €
Add to cart
Brand: Vents
The mixing unit for ventilation Vents USVK-1-6 is designed to ensure circulation and control the temperature of water (water mixtures) used as a coola..
from
1,378.48 €
Ex Tax:1,139.24 €
Add to cart
Brand: Vents
The mixing unit for ventilation Vents USVK-3/4-4 is designed to ensure circulation and control the temperature of water (water mixtures) used as a coo..
from
717.39 €
Ex Tax:592.89 €
Add to cart
Brand: Vents
The Vents MPA 2500 V unit with a water heater is intended for use as part of a supply ventilation system. The supply unit is capable of supplying outs..
from
4,219.82 €
Ex Tax:3,487.46 €
Add to cart