Share
The Vents VKPI 4E 600x300 fan is a single-phase duct fan with a channel cross-section of 600x300 mm. The maximum productivity of this model is2470 m3/h. The fan uses 50 mm mineral wool sound insulation. It is advisable to use such fans for ventilation of rooms with high noise level requirements. It is also recommended to provide additional measures for noise reduction - the use of noise suppressors before and after the fan, installation of noise suppressors directly into the walls, etc.
Technical characteristics
Parameter | Value |
Voltage, V | 230 |
Current , A | 0.9 |
Current frequency, Hz | 50 |
220 | tr>|
Capacity, m3/h | 2470 |
Rotation speed, min-1 | 1400 |
Noise level at a distance of 3 m, dB(A) | 47 |
Maximum temperature of transported air , C | -25...+45 |
Weight, kg | 52.5 td> |
Protection, class | IPХ4 |
Pipe size, mm | 600x300 |
Overall dimensions
Dimensions | B | B1 | B2 | B3 | H | H1 | < strong>H2 | H3 | < td style='text-align: center, background-color: #b7c0c2,'>L|
mm | 600 | 620 | 640 | 700 | 300 | 320 | 340 | 460 | 680 |
Diagram
Design
The Vents VKPI 4E 600x300 fan housing is made of galvanized steel. VKPI models have a layer of sound and heat insulation made of mineral wool 50 mm thick.
Motor
2- and 4-pole asynchronous motors with an external rotor are used, which have an impeller with backward-curved blades made of galvanized steel. To provide thermal protection against overheating, thermal contacts with automatic restart or with terminals for connecting external protection devices are built into the motor windings (depending on the model, see connection diagrams).
The use of rolling bearings in engines ensures a long service life. To achieve precise performance, low noise levels and safe fan operation, each turbine undergoes dynamic balancing during assembly. The motor in the fan has a protection class of IP 44.
Speed adjustment
Adjustment can be either smooth or stepwise, and is carried out using a triac or autotransformer regulator. Fans can be connected several at a time to one control device, provided that the total power and operating current do not exceed the rated parameters of the controller.
Installation
The fans are mounted in the gap of rectangular air ducts and do not require special fastening if the connection is made directly to them. In the case of connection through flexible inserts, it is necessary to fasten it to the building structure using supports, hangers or brackets.
The fan can be installed in any position, taking into account the direction of air flow (indicated by an arrow on the fan housing). It is also necessary to provide access for servicing the fan. Power is supplied to the fan through external terminals. For inspection and maintenance, a technological cover is provided on the fan housing.
Documentation
Characteristic | |
Voltage | 220 V |
Efficiency | 2470 cubic meters/hour |
The size of the rectangular channel | 600x300 mm |
The product will be manufactured after making a payment or a 50% advance payment.
Online payment methods: Bizum, Apple Pay, Mastercard, Visa.
For payments to the bank account of VIP Ventanas SL company: SWIFT, SEPA.
It is possible to make the payment without VAT if the product is delivered outside of Spain.
Delivery is carried out by the company's own transportation or delivery service.