Share
The Vents VKPF 6D 1000x500 fan is a duct fan and is used for use as part of a supply or exhaust ventilation system. Connects to other ventilation elements with a cross-section of 1000x500 mm. The fan can move air with temperatures ranging from -20°C to +55°C. This fan model is equipped with a three-phase motor, the fan's performance can be adjusted using a frequency regulator or a step transformer (not included in the delivery package, purchased separately).
Specifications
Parameter | Value |
Voltage, V | 400 |
Current, A | 7 |
Current frequency, Hz | 50 |
Maximum power, W | 3870 |
Productivity, m3/h | < td style='text-align: center,'>9540 |
Rotation speed, min-1< br> | 930 |
Noise level at a distance of 3 m, dB(A) | 61 |
Maximum temperature of transported air, C | -20...+55 |
Weight, kg | 95 |
Protection, class | IPX4 |
Pipe size, mm < /strong> | 1000x500 |
Number of poles | 6 |
Overall dimensions
< p>Dimensions | B | B1 | B2 | H | H1 | H2 | H3 | L | tr>
mm td> | 1000 | 1020 | 1040 | 500 | 520 | 540 | 580 | 954 |
Diagram
< /br>
Design
The Vents VKPF 6D 1000x500 fan housing is made of galvanized steel.
Motor
4 and 6 pole asynchronous motors with an external rotor and a galvanized steel impeller with forward curved blades are used. Fans with this turbine design are characterized by high performance and a relatively large pressure drop.
To provide thermal protection against overheating, thermal contacts with terminals for connecting external protection devices are built into the motor winding. The use of rolling bearings in engines ensures a long service life. To achieve precise performance, low noise levels and safe fan operation, each turbine undergoes dynamic balancing during assembly. The motor in the fan has a protection class of IP 44.
Speed adjustment
Adjustment can be either smooth or stepwise, and is carried out using a triac or autotransformer regulator. Several fans can be connected to one control device at once, provided that the total power and operating current do not exceed the rated parameters of the controller.
The fan speed control not only makes it possible to save money by reducing energy consumption and extending the service life of the electric motor, but also significantly reduces the noise from the fan when maximum power is not needed. Adjustment is especially often used in supply ventilation systems during the cold season, since heating a smaller amount of supply air requires less energy.
Installation
The fans are mounted through flexible inserts, it is necessary to fasten it to the building structure using supports, hangers or brackets.
The fan can be installed in any position, taking into account the direction of air flow (indicated by an arrow on the fan housing). It is also necessary to provide access for servicing the fan. Power is supplied to the fan through external terminals. For inspection and maintenance, the fan is equipped with a technological cover on the housing.
Installation example
Documentation
Characteristic | |
Voltage | 400 V |
Efficiency | 9540 cubic meters/hour |
The size of the rectangular channel | 1000x500 mm |
The product will be manufactured after making a payment or a 50% advance payment.
Online payment methods: Bizum, Apple Pay, Mastercard, Visa.
For payments to the bank account of VIP Ventanas SL company: SWIFT, SEPA.
It is possible to make the payment without VAT if the product is delivered outside of Spain.
Delivery is carried out by the company's own transportation or delivery service.