Menu
Menu
Your Cart

Fan Vents VKPFI 4D 800x500

 Fan Vents VKPFI 4D 800x500

Share

The Vents VKPFI 4D 800x500 fan is equipped with a noise-insulated housing. For sound insulation, 50 mm mineral wool is used. The fan is equipped with a three-phasemotor, maximum performance - 8120 m3/h. Connects to air ducts with a cross-section of 800x500 mm.

Technical characteristics

< tr>
Parameter Value
Voltage, V

400
Current, A 9.35

Current frequency, Hz 50
Maximum power, W

< /strong>
5850
Productivity, m3/h< br>
8120
Rotation speed, min-1

1140 < /td>
Noise level at a distance of 3 m, dB(A)

61
Maximum temperature of transported air, C

-25...+40

Weight, kg 127
Protection, class

IPХ4
Pipe size, mm

800x500
Number of poles 4

Dimensions

'Drawing

Dimensions B B1 B2 B3 H H1 H2 H3 L
mm 800 820 840 900 500 520 540 720 935

Charts

< img src='/image/vent/vkpf4d800_500.jpg' alt='Aerodynamic characteristics of Vents VKPFI 4D 800x500'>

Design

The Vents VKPFI 4D 800x500 fan housing is made of galvanized steel. VKPFI models have a layer of sound and heat insulation made of mineral wool 50 mm thick.

Motor

4 and 6-pole asynchronous motors with an external rotor and a galvanized steel impeller with forward curved blades are used. Fans with this turbine design are characterized by high performance and a relatively large pressure drop. To provide thermal protection against overheating, thermal contacts with terminals for connecting external protection devices are built into the motor winding. The use of rolling bearings in engines ensures a long service life. To achieve precise performance, low noise levels and safe fan operation, each turbine undergoes dynamic balancing during assembly. The motor in the fan has a protection class of IP 44.

Speed adjustment

Adjustment can be either smooth or stepwise, and is carried out using a triac or autotransformer regulator. Several fans can be connected to one control device at once, provided that the total power and operating current do not exceed the rated parameters of the controller.

Installation

The fans are mounted in the gap of rectangular air ducts and do not require special fastening if the connection is made directly to them. In the case of connection through flexible inserts, it is necessary to fasten it to the building structure using supports, hangers or brackets. The fan can be installed in any position, taking into account the direction of air flow (indicated by an arrow on the fan housing). It is also necessary to provide access for servicing the fan. Power is supplied to the fan through external terminals. For inspection and maintenance, the fan is equipped with a technological cover on the housing.

Installation example

'Warehouse

Documentation

'VKPFI

Characteristic
Voltage 400 V
Efficiency 8120 cubic meters/hour
The size of the rectangular channel 800x500 mm

The product will be manufactured after making a payment or a 50% advance payment.

Online payment methods: Bizum, Apple Pay, Mastercard, Visa.

For payments to the bank account of VIP Ventanas SL company: SWIFT, SEPA.

It is possible to make the payment without VAT if the product is delivered outside of Spain.

Delivery is carried out by the company's own transportation or delivery service.

Write a review