Vents VUT 1000 G

Vents VUT 1000 G is an air handling unit with heat recovery without the use of a heater. It is used to create supply and exhaust ventilation for residential and commercial premises where it is impossible to use installations with electric or water heaters. The maximum consumption of the installation is only820 Wper hour.

The nominal capacity of this model is1200 m3/hIn the cold season, the unit’s productivity is lower, since in order to ensure the required supply air temperature in this unit, the supply fan is periodically turned off by the heat exchanger protection system . This process is described in more detail below in the Recuperator section.

The unit is intended for installation indoors with positive temperatures, the diameter of the air duct connection is 250 mm.

Casing

The unit casing is made of aluminum profile and sandwich panels with internal heat and sound insulation made of mineral wool 20 mm thick.

Filter

To filter supply and exhaust air, the unit has two built-in filters with a cleaning degree of G4 (exhaust) and F7 (supply).

Fans

The Vents VUT 1000 G unit is equipped with supply and exhaust double-suction centrifugal fans with forward-curved blades and a built-in protection thermostat with automatic restart. Electric motors and impellers are dynamically balanced in two planes. Rolling ball bearings of electric motors do not require maintenance; their service life is at least 40,000 hours.

Recuperator

The cross-current recuperator is made of aluminum plates. For operation of the unit without recuperation, a “summer” liner is provided. Under the recuperator block there is a tray for collecting and discharging condensate. The supply and exhaust unit is equipped with a built-in system for protecting the recuperator from freezing during the cold season. Its essence is that the temperature sensor turns off the supply fan and the warm exhaust air warms up the recuperator. Then the supply fan turns on and the entire installation operates as usual.

Control

The fan rotation speed is controlled using a four-position switch, which allows you to select minimum, average or maximum speed or turn off the unit.

Specifications

Parameter Value
Voltage, V

230
Current frequency, Hz 50

Maximum fan power, W 2x410
Total power of the installation, W 820
Total current, A 3.6
Productivity, m3/h

1200

Rotation speed, min-1

1850
< strong>Noise level at a distance of 3 m, dB(A)

60
Maximum temperature of transported air, C

-25....+40

Weight, kg 85
Size of connected air duct, mm

250

Overall dimensions

'Installation

Dimensions D B B1 B2 B3 H H1 H2 L L1
mm 248 548 496 60 213 794 290 200 802 850

Diagram

'Aerodynamic

Installation of the VUT G installation

The air handling unit is mounted on the floor, suspended from the ceiling using mounting bracket with vibration insert or mounted on the wall using brackets. The installation can be placed both in auxiliary rooms and in the main ones (behind a suspended ceiling, in a niche or in an open way). It can only be installed in such a position as to ensure collection and drainage of condensate. Access for service and filter cleaning is from the side panels.

Documentation

'Installation

Characteristic
Efficiency 1200 cubic meters/hour
Duct diameter 250 mm

The product will be manufactured after making a payment or a 50% advance payment.

Online payment methods: Bizum, Apple Pay, Mastercard, Visa.

For payments to the bank account of VIP Ventanas SL company: SWIFT, SEPA.

It is possible to make the payment without VAT if the product is delivered outside of Spain.

Delivery is carried out by the company's own transportation or delivery service.

Write a review

Please login or register to review